Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Maximum continuous voltage UC | 30 V DC |
21 V AC |
Rated current | 600 mA (56 °C) |
Operating effective current IC at UC | ≤ 5 µA |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In (8/20) µs (line-line) | 5 kA |
Nominal discharge current In (8/20) µs (line-ground) | 5 kA |
Nominal discharge current In (8/20) µs (line-signal ground) | 5 kA |
Pulse discharge current Iimp (10/350) µs (line-line) | 0.5 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 0.5 kA |
Pulse discharge current Iimp (10/350) µs (line-signalground) | 0.5 kA |
Total discharge current Itotal (8/20) µs | 10 kA |
Voltage protection level Up (line-line) | ≤ 200 V (C1 - 1 kV / 500 A) |
≤ 320 V (C2 - 10 kV / 5 kA) |
≤ 50 V (C3 - 25 A) |
≤ 55 V (C3 - 100 A) |
Voltage protection level Up (line-earth) | ≤ 900 V (C1 - 1 kV / 500 A) |
≤ 1.05 kV (C2 - 10 kV / 5 kA) |
≤ 1.3 kV (C3 - 25 A) |
≤ 1.4 kV (C3 - 100 A) |
Voltage protection level Up (line-signalground) | ≤ 750 V (C1 - 1 kV / 500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) |
≤ 700 V (C3 - 25 A) |
≤ 750 V (C3 - 100 A) |
Voltage protection level Up static (line-line) | ≤ 50 V (C1 - 1 kV / 500 A) |
≤ 120 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up static (line-earth) | ≤ 900 V (C1 - 1 kV / 500 A) |
≤ 1.05 kV (C2 - 10 kV / 5 kA) |
Voltage protection level Up static (line-signalground) | ≤ 750 V (C1 - 1 kV / 500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-earth) | ≤ 100 ns |
Response time tA (line-signalground) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 250 kHz / 150 Ω) |
Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 940 kHz |
Capacity (Core-Core) | typ. 2.2 nF |
Resistance per path | 1.65 Ω ±20 % |
Surge protection fault message | optical |
Max. required back-up fuse | 630 mA (FF) |
Impulse durability (line-line) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA |
C3 - 100 A |
Impulse durability (line-earth) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA |
C3 - 100 A |
D1 - 500 A |
Impulse durability (line-signalground) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA |
C3 - 100 A |
D1 - 500 A |
Pulse reset time (line-line) | ≤ 700 ms |
Pulse reset time (line-earth) | ≤ 30 ms |
Pulse reset time (line-signalground) | ≤ 1500 ms |
Additional technical data |
Max. total discharge current I total max (8/20) µs | 20 kA (1x) |